Guangzhou Zhongxin Automation Technology Co., Ltd. specializes in supplying F1 sensors ranging from F1-100kg to F1-20t_
Italian AEP weighing sensor,
Italian AEPThe series guarantees fast delivery time and 100% original imports, providing a complete automated weighing solution for various industrial fields. Italian AEP weighing sensor range: F1-2.5kg, F1-5kg, F1-10kg, F1-20kg, F1-25kg, F1-50kg, F1-100kg, F1-200kg. Italian AEP is one of our key advantageous products, with absolute competitive prices, in stock, original, authentic, and reliable! Ensure satisfactory price and quality! We solemnly promise: "If you are not satisfied within three months, you can return or exchange the goods unconditionally at any time, refund the full payment, and do not charge any fees.". Two years warranty, free maintenance at any time!
Product features:
Bellows type weighing sensorStainless steel material, sealed welding
Protection level IP67
Accuracy level: OIML R60 C2/C3
ATEX optional: II 2 G Ex ib IIC T6 II 2 D Ex ibD 21 T70 ° C
Range: 2.5, 5, 10, 20, 25, 50100200 kg
Technical parameters:

Product size:
Expand reading
Weighing Module
Installation instructions
Mechanical installation If necessary, shims can be used to adjust the force evenly on each sensor.
The top and bottom plates of the weighing module must be adjusted in a straight line to maintain the vertical direction of the force acting on the sensor.
When welding near the weighing module, be sure to pay attention to grounding, otherwise the welding current will pass through the sensor and cause damage.
The basic requirements are horizontal and have good rigidity, and there is a small difference in the required levelness between the foundations.
Be sure to tighten the support bolts of the weighing module during installation.
The weighing module must be installed in a convenient maintenance location.
ConnectionAll connections should use shielded insulated cables.
Electromagnetic interference can affect the output signal of sensors, causing weighing errors.
Isolate the power cord and sensor cable.
The junction box should be protected from moisture and corrosive substances.
Cables can be fitted with sleeves to prevent mechanical damage or erosion by damp or corrosive substances.
Do not arbitrarily change the length of the sensor cable, as this will change the output impedance of the sensor.
It is recommended to choose the recommended length and size of the connecting cable between the junction box and the weighing instrument, otherwise it may cause signal loss.
Preparation work before calibration Install brackets on the tank body for hanging weights. The spacing between each bracket should be equal.
Before calibration, the output signal of each sensor should be tested to determine whether the force is evenly distributed to each sensor.
If necessary, the level of the module can be adjusted with a gasket or the potentiometer of the junction box can be adjusted to maintain consistent output for each sensor.
The above are [F1 sensor] F1-100kg~F1-20t_ Detailed information on Italian AEP weighing sensors, if you are interested in [F1 sensor] F1-100kg~F1-20t_ If you have any questions about the price, delivery time, model, or inventory of AEP weighing sensors in Italy, please feel free to call us
18520271262 Chen GongObtain 【 F1 Sensor 】 F1-100kg~F1-20t_ Italian AEP
Weighing sensorLatest price details for.